One of the most important indicators of floor coverings is the flame propagation on the surface (FP).
Thus the polyvinylchloride coverings “SOLD” are permitted for using in corridors and halls while linoleum has high fire danger rating (КМ4 and КМ5) and can’t be used on the ways of evacuation.
“Technical Regulations of Fire Safety Requirements” (Russian Federal Law No.123-FZ from 22 July 2008)
Class (subclass) of functional fire danger of building* |
Number of floors and height of building |
Fire danger rating, no more than stated |
|
For floor covering | |||
Lobbies, stairwells, lift halls |
Corridors, halls, lobbies |
||
Ф1.2; Ф1.3; Ф2.3; Ф2.4; Ф3.1; Ф3.2; Ф3.6; Ф4.2; Ф4.3; Ф4.4; Ф5.1; Ф5.2; Ф5.3 |
No more than 9 floors or no more than 28 m |
КМ3 | КМ4 |
More than 9 floors, but fewer than 17 floors sor more 28 m but no more than 50 m |
КМ2 | КМ3 | |
More than 17 floors or more than 50 m |
КМ1 | КМ2 | |
Ф1.1; Ф2.1; Ф2.2; Ф3.3; Ф3.4; Ф3.5; Ф4.1 |
Doesn’t depend on number of floors or height |
КМ1 | КМ2 |
Class (subclass) of functional fire danger of building |
Capacity of halls/person | Material class, no more than stated |
For floor covering | ||
Ф1.2; Ф2.3; Ф2.4; Ф3.1; Ф3.2; Ф3.6; Ф4.2; Ф4.3; Ф4.4; Ф5.1 |
More than 800 |
КМ2 |
More than 300, but no more than 800 |
КМ2 | |
More than 50, but no more than 300 |
КМ3 | |
No more than 50 | КМ4 | |
Ф1.1; Ф2.1; Ф2.2; Ф3.3; Ф3.4; Ф3.5; Ф4.1 |
More than 300 | КМ2 |
More than 15, but no more than 300 |
КМ2 | |
No more than 15 | КМ4 |